Transports

A transport is a configured protocol connection. It is declared once and shared across all devices that speak the same protocol on the same network endpoint.

The transport owns the connection lifecycle: it opens it, keeps it alive, and closes it. Individual device reads and writes are dispatched through it without managing connectivity per device.


Connection lifecycle

Each transport goes through the following states:

State Description
idle Initialised, not yet connected
connecting Connection attempt in progress
connected Ready to read and write
connection_error Last connection attempt failed
closing Graceful shutdown in progress
closed Connection released

Every read and write is gated by a connected guard: if the transport is not in the connected state when an operation is issued, a connection attempt is made automatically before proceeding. If the attempt fails, the state moves to connection_error and the operation is still attempted — the error surfaces to the caller.

Updating a transport's config triggers an automatic reconnect — the transport closes the current connection and reopens it with the new settings.


Configuration per protocol

HTTP

HTTP is stateless — each read or write sends a new HTTP request. The transport holds a shared async HTTP client that is initialised on connect and reused across requests.

Field Required Default Description
request_timeout no 10 Timeout in seconds applied to every HTTP request

MQTT

MQTT maintains a persistent connection to a broker. It is push-based: on connect, the transport starts a background message loop that dispatches incoming messages to registered attribute listeners. Any message arriving on a topic that matches a registered attribute's read topic will be parsed through that attribute's codecs and used to update its value — regardless of whether the message was triggered by a read request. In practice, the MQTT transport largely works by listening to topics corresponding to registered device attributes.

Read flow — the transport publishes a request message to request.topic, subscribes to the response topic, and waits up to 10 seconds for a message to arrive. If no message is received within that window, the read times out. The request field in the transport address controls what is published and where.

Write flow — the transport publishes the rendered message to topic as defined in the write address.

Field Required Default Description
host yes Hostname or IP address of the MQTT broker
port no 1883 TCP port of the MQTT broker

Modbus TCP

Modbus TCP maintains a persistent TCP connection to the Modbus server (PLC or gateway). Reads and writes are pull-based: the transport issues a Modbus function code request and waits for a response.

Field Required Default Description
host yes Hostname or IP address of the Modbus server
port no 502 TCP port of the Modbus server

BACnet

BACnet creates a local BACnet/IP application bound to the specified network interface. The ip_with_mask identifies that interface. The transport sends and receives BACnet packets over UDP.

Field Required Default Description
ip_with_mask yes Local interface IP with subnet mask (e.g. 192.168.1.100/24)
port no 47808 UDP port for BACnet/IP
local_device_instance no 990001 BACnet device instance of the Gridone client on the network
local_device_name no "GridOne BACnet Client" BACnet device name of the Gridone client
max_apdu_length no 1024 Maximum APDU length in bytes
vendor_identifier no 999 BACnet vendor identifier
segmentation_supported no noSegmentation Segmentation support level
discovery_timeout no 10.0 Timeout in seconds for device discovery
read_property_timeout no 5.0 Timeout in seconds for read operations
write_property_timeout no 5.0 Timeout in seconds for write operations
default_write_priority no 8 Default BACnet write priority (516) used when no priority is specified in the address

KNX

KNX uses the KNX/IP tunneling protocol to communicate with a KNX/IP gateway. It is push-based: on connect, a background listener processes all incoming telegrams. Any GroupValueResponse or GroupValueWrite received on a registered group address is immediately dispatched and updates the corresponding attribute value.

Read flow — sends a GroupValueRead telegram to the group address and awaits a GroupValueResponse. If no response is received within 5 seconds, the read times out.

Write flow — sends a GroupValueWrite telegram to the group address.

Field Required Default Description
gateway_ip yes Hostname or IP address of the KNX/IP gateway (no protocol prefix)
port no 3671 UDP or TCP port of the KNX/IP gateway
tunneling_mode no "udp" Tunneling transport: "udp" or "tcp"
secure_credentials no KNX Secure credentials — if set, always uses TCP Secure regardless of tunneling_mode

secure_credentials fields:

Field Required Default Description
device_authentication_password yes KNX Secure device authentication password
user_password yes KNX Secure user password
user_id no 2 KNX Secure user ID